IntelliRupter® PulseCloser® Fault Interrupter

Distribution faults damage your equipment, reliability, and bottom line. In fact, your current fault-management strategy may cause more damage than you realize by multiplying the force applied to your system when testing the line for faults after an event.

S&C’s IntelliRupter PulseCloser Fault Interrupter uses PulseClosing® Technology todramatically reduce the amount of force used during fault testing and to significantly lessen momentary outages for customers on the main feeder. This strategy improves reliability and reduces costs for you and your customers.The IntelliRupter fault interrupter’s accurate sensing and directional capabilities will help with the increase of distributed energy installations, while PulseClosing® Technology solves the problem of stress caused by conventional reclosing.

Key Constructional & Operational Details:

IntelliRupter fault interrupters are factory-assembled on a stainless-steel base and include:

 

  • Unique magnetic latching actuators for the interrupters, providing single-phase tripping/single-phase lockout, single phase tripping/three-phase lockout, or three-phase tripping/ three-phase lockout (The interrupters can be manually tripped by means of a manual lever. Operable from the ground with an extend stick (overhead models), or they can be manually tripped by means of a manual OPEN/CLOSE/ READY lever (pad mount models)
  • High-accuracy sensors, for three-phase monitoring of line current and three-phase monitoring of line voltage on both sides of the interrupters (Sensing accuracy is ±0.5% for both voltage and current. Total system accuracy for fault detection, including sensing, control, and interrupting time, is ±2%.)
  • External power supply connector, permitting pre-installation uploading and downloading of configuration settings, plus radio programming and battery charging, as applicable, indoors in your service center or lab
  • Unique multi-function status indicator, which shows that the control group is operating normally (The blink rate changes when a Wi-Fi connection is made, control power is lost, or the position of the OPEN/CLOSE/READY lever is changed. A separate HOT LINE TAG indicator shows a “set” tag.)

Integrated Global Positioning System, providing 1-ms accurate time-stamping of events to speed post-event analysis as well as IntelliRupter fault interrupter location data for entry into your graphical information system.

Advantages

Medium to large sized

transformers

Utility and industrial transformers

Transmission

transformers

Other Product Details

Fault interruption, fault isolation, and circuit restoration in a single, easy-to-install package.

  • Unique PulseClosing® Technology confirms there’s no fault on the line before initiating point-on-wave closing
  • Vacuum interrupters with a unique actuating system that enables PulseClosing® Technology
  • Integrated three-phase voltage sensing on both sides of the interrupters

 

  • Integrated three-phase current sensing that provides linear output over the range from load to fault current
  • An integrated power module on one or both sides of the interrupters, eliminating the need to install separate power transformers
  • Solid dielectric insulation featuring S&C’s Cypoxy Insulator, a cycloaliphatic epoxy resin system
  • Models with or without integrated visible disconnect
  • A choice of integrated controls, all configurable from the safety of your vehicle using a Wi-Fi link to your PC:
    • A standard Control Group provides basic protective functionality in standalone applications
    • An IntelliTeam® SG Control Group supports S&C’s IntelliTeam SG Automatic Restoration System
    • All controls are line-powered, so no VT needed
    • All controls are hookstick-replaceable
  • Internal circuit-making and circuit-breaking for all-weather reliability (hookstick-operated disconnect with air gap)
  • Integrated three-phase voltage and current sensors that eliminate cost, clutter, and complexity of separately mounted sensors

Disconnect Styles

kV 

Amperes RMS

Max

BIL

Continuous

Interrupting Symmetrical

15.5

110

800/900

16 000

27

125

800/900

12 500

38

170

630/800

12 500

Compact Styles

kV 

Amperes RMS

Max

BIL

Continuous

Interrupting Symmetrical

15.5

95

800/900

16 000

27

125

800/900

12 500

 

 

Non-Disconnect Styles

kV 

Amperes RMS

Max

BIL

Continuous

Interrupting Symmetrical

15.5

110

800/900

16 000

27

125

800/900

12 500

38

170

630/800

12 500